E6581158
F-75
6
6.21.2 Changing the display unit to A/V/min
-1
H :Current/voltage display mode
• Function
These parameters are used to change the unit of monitor display.
% ⇔ A (ampere)/V (volt)
Q Example of setting
During the operation of the VFS11-2037PM (rated current: 17.5A) at the rated load (100% load), units are
displayed as follows:
1) Display in percentage terms 2) Display in amperes/volts
[
[[
[
E
EE
E
E
EE
E
[
[[
[
Output current:
17.5A
DC voltage:
200V (value
converted into
AC)
DC voltage:
ųų100%
Output current:
ųų100%
%
%
Title Function Adjustment range Default setting
H
Current/voltage
display mode
0: %
1: A (ampere)/V (volt)
0
* The H converts the following parameter settings:
• A display Current monitor display
Motor electronic-thermal protection level 1 and 2
VJT, H
DC braking current H
Stall prevention level 1 and 2 H, H
Small current detection current H
Step-out detection current level H
(for PM motors)
• V display Voltage monitor display
Note) Base frequency voltage 1 and 2 I(XNX, H)s always displayed in the unit of V.