3) Increasing starting torque
Setting of V/F control mode selection RV to (automatic torque boost control)
Detects load current in all speed ranges and automatically adjusts voltage output (torque boost) from inverter.
This gives steady torque for stable runs.
ųųųAutomatically
adjusts the
amountof torque
boost
Output voltage(%)
Base frequencyvoltage
XNX
Output frequency(Hz)Base frequency XN
0
Note: This control system can oscillate and destabilize runs depending on the load. If that should
happen, set V/F control mode selection RV to (V/F constant) and increase torque manu-
ally.
+ Motor constant must be set
If the motor you are using is a 4P Toshiba standard motor and if it has the same capacity as the inverter,
there is basically no need to set the motor constant. In any other case, be sure to set the parameters H
to H properly.
Be sure to set H (rated current of motor) and H (rated speed of motor) correctly, as specified on
the motor’s nameplate. For the setting of H (no-load current of motor), refer to the motor test report.
There are three procedures for setting the other motor constants.
1) Auto torque boost and a motor constant (auto-tuning) can be set at once.
To do so, set the basic parameter CW to . For details, see 1 in 5.2.
2) The motor constant can be automatically set (auto-tuning). Set the extended parameter H to .
For details, see selection 2 in 6.17.
3) Each motor constant can be set individually. For details, see selection 3 in 6.17.
4) Vector control - increasing starting torque and achieving high-precision operation.
Setting of V/F control RV to (Vector control)
Using sensor-less vector control with a Toshiba standard motor will provide the highest torque at the low
speed ranges.
(1) Provides large starting torque.
(2) Effective when stable operation is required to move smoothly up from the low speeds.
(3) Effective in elimination of load fluctuations caused by motor slippage.

Table of Contents

Other manuals for Toshiba TOSVERT VF-S11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S11 and is the answer not in the manual?

Toshiba TOSVERT VF-S11 Specifications

General IconGeneral
ModelTOSVERT VF-S11
CategoryInverter
Output Frequency0.1-400Hz
Frequency Range0.1-400Hz
Control MethodV/f Control, Sensorless Vector Control
Power Rating0.2kW to 15kW
Cooling MethodForced air cooling
Overload Capacity150% for 60 seconds
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationModbus RTU
Input Voltage200-240V, 380-480V
Braking UnitBuilt-in (optional external braking resistor)

Related product manuals