Table 37: Output signals, G2.3
Index Parameter Min Max Unit Default Cust ID Description
P2.3.11
Output frequency
limit 1; Supervised
value
0.00 320.00 Hz 0.00 316
P2.3.12
Output frequency
limit 2 supervision
0 2 0 346
0 = No limit
1 = Low limit
supervision
2 = High limit
supervision
P2.3.13
Output frequency
limit 2; Supervi-
sion value
0.00 320.00 Hz 0.00 347
P2.3.14
Torque limit
supervision func-
tion
0 2 0 348
0 = No
1 = Low limit
2 = High limit
P2.3.15
Torque limit
supervision value
-300.0 300.0 % 100.0 349
P2.3.16
Reference limit
supervision func-
tion
0 2 0 350
0 = No
1 = Low limit
2 = High limit
P2.3.17
Reference limit
supervision value
0.0 100.0 % 0.0 351
P2.3.18
External brake
Off-delay
0.0 100.0 s 0.5 352
P2.3.19
External brake
On-delay
0.0 100.0 s 1.5 353
P2.3.20
Frequency con-
verter tempera-
ture limit supervi-
sion
0 2 0 354
0 = No
1 = Low limit
2 = High limit
P2.3.21
Frequency con-
verter tempera-
ture supervised
value
-10 100 °C 40 355
P2.3.22
Analogue output 2
scaling
0.1 E.10 0.1 471
TTF programming
method used. See
Chapter 8.9 "Ter-
minal to function"
(TTF) programming
principle.
PID CONTROL APPLICATION VACON · 113