Table 61: Digital inputs (Control keypad: Menu M2 -> G2.2.4)
Index Parameter Min Default Cust ID Description
P2.2.7.21 *
Parameter set 1/set 2
selection
0.1 0.1 496
Closed cont.=Set 2 is used
Open cont.= Set 1 is used
P2.2.7.22 * Motor control mode 1/2 0.1 0.1 164
Closed cont.= Mode 2 is used
Open cont.= Mode 1 is used
See parameter 2.6.1, 2.6.12
NXP drives only
P2.2.7.23 * Cooling monitor 0.1 0.2 750 Used with liquid-cooled unit.
P2.2.7.24 *
External brake acknowl-
edge
0.1 0.2 1210
Monitoring signal from
mechanical brake.
P2.2.7.26 * Enable inching 0.1 0.1 532 Enables Inching function.
P2.2.7.27 * Inching reference 1 0.1 0.1 530
Inching reference 1. (Default
Forward 2 Hz. See P2.4.15).
This will start the drive.
P2.2.7.28 * Inching reference 2 0.1 0.1 531
Inching reference 2. (Default
Forward 2 Hz. See P2.4.16).
This will start the drive.
P2.2.7.29 * Reset encoder counter 0.1 0.1 1090
Reset Shaft Rounds and
Angle (see 6-3).
P2.2.7.30 * Emergency stop 0.1 0.2 1213 Low signal activates EM.
P2.2.7.31 * Master Follower mode 2 0.1 0.1 1092
See Chapter 8.2 Master/
follower function (NXP only)
and parameters P2.11.1-
P2.11.7.
P2.2.7.32 *
Input switch acknowledge-
ment
0.1 0.2 1209
Low signal generates fault
(F64).
cc = closing contact
oc = opening contact
* = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle).
VACON · 154 MULTI-PURPOSE CONTROL APPLICATION
6
TEL. +358 (0)201 2121 · FAX +358 (0)201 212 205

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled

Related product manuals