Table 85: Basic parameters G2.1
Index Parameter Min Max Unit Default Cust ID Description
P2.1.16 Sleep delay 0 3600 s 30 1017
The minimum
quantity of time
during which the
frequency has to
stay below the
sleep level before
the drive stops.
P2.1.17 Wake up level 0.0 1000.0 % 25.0 1018
Gives the level for
the PID feedback
value wake-up
supervision. Uses
the set process
units.
P2.1.18 Wake up function 0 3 0 1019
0 = Wake-up at fall
below wake up
level (P2.1.17)
1 = Wake-up at
exceeded wake up
level (P2.1.17)
2 = Wake-up at fall
below wake up
level (P3.4/3.5)
3 = Wake-up at
exceeded wake up
level (P3.4/3.5)
P2.1.19
Jogging speed
reference
0.00 P2.1.2 Hz 10.00 124
* = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle).
PUMP AND FAN CONTROL APPLICATION VACON · 205