Table 86: Basic Settings (Control keypad: Menu M2 -> G2.2.1)
Index Parameter Min Max Unit Default Cust ID Description
P2.2.1.15
Motor potentiom-
eter ramp time
0.1 2000.0 Hz/s 10.0 331
P2.2.1.16
Motor potentiom-
eter frequency
reference mem-
ory reset
0 2 1 367
0 = No reset
1 = Reset if stop-
ped or powered
down
2 = Reset if pow-
ered down
P2.2.1.17
Motor potentiom-
eter PID reference
memory reset
0 2 0 370
0 = No reset
1 = Reset if stop-
ped or powered
down
2 = Reset if pow-
ered down
P2.2.1.18
B reference scale,
minimum
0.00 320.00 Hz 0.00 344
0 = Scaling off
>0 = Scaled min.
value
P2.2.1.19
B reference scale,
maximum
0.00 320.00 Hz 0.00 345
0 = Scaling off
>0 = Scaled min.
value
* = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle).
VACON · 208 PUMP AND FAN CONTROL APPLICATION