Table 87: Analogue input 1 (Control keypad: Menu M2 -> G2.2.2)
Index Parameter Min Max Unit Default Cust ID Description
P2.2.2.1
**
AI1 signal selec-
tion
0.1 E.10 A.1 377
TTF programming.
See Chapter 8.9
"Terminal to func-
tion" (TTF) pro-
gramming principle.
P2.2.2.2 AI1 filter time 0.00 10.00 s 0.10 324 0 = No filtering
P2.2.2.3 AI1 signal range 0 2 0 320
0 = 0-10 V (0-20
mA*)
1 = 2-10 V (4-20
mA*)
2 = Customised *
P2.2.2.4
AI1 custom mini-
mum setting
-160.00 160.00 % 0.00 321
P2.2.2.5
AI1 custom maxi-
mum setting
-160.00 160.00 % 100.00 322
P2.2.2.6
AI1 signal inver-
sion
0 1 0 323
0 = Not inverted
1 = Inverted
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle)
PUMP AND FAN CONTROL APPLICATION VACON · 209