Table 88: Analogue input 2 (Control keypad: Menu M2 -> G2.2.3)
Index Parameter Min Max Unit Default Cust ID Description
P2.2.3.1
**
AI2 signal selec-
tion
0.1 E.10 A.2 388
TTF programming.
See Chapter 8.9
"Terminal to func-
tion" (TTF) pro-
gramming principle.
P2.2.3.2 AI2 filter time 0.00 10.00 s 0.10 329 0 = No filtering
P2.2.3.3 AI2 signal range 0 2 1 325
0 = 0-10 V
(0-20mA*)
1 = 2-10 V (4-20
mA*)
2 = Customised *
P2.2.3.4
AI2 custom mini-
mum setting
-160.00 160.00 % 0.00 326
P2.2.3.5
AI2 custom maxi-
mum setting
-160.00 160.00 % 100.00 327
P2.2.3.6 AI2 inversion 0 1 0 328
0 = Not inverted
1 = Inverted
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle).
VACON · 210 PUMP AND FAN CONTROL APPLICATION