Table 89: Analogue input 3 (Control keypad: Menu M2 -> G2.2.4)
Index Parameter Min Max Unit Default Cust ID Description
P2.2.4.1
**
AI3 signal selec-
tion
0.1 E.10 0.1 141
TTF programming.
See Chapter 8.9
"Terminal to func-
tion" (TTF) pro-
gramming principle.
P2.2.4.2 AI3 filter time 0.00 10.00 s 0.10 142 0 = No filtering
P2.2.4.3 AI3 signal range 0 2 1 143
0 = 0-10 V
(0-20mA*)
1 = 2-10 V (4-20
mA*)
1 = Customised *
P2.2.4.4
AI3 custom mini-
mum setting
-160.00 160.00 % 0.00 144
% of input signal
range. e.g. 2 mA =
10 %
P2.2.4.5
AI3 custom maxi-
mum setting
-160.00 160.00 % 100.00 145
e.g. 18 mA = 90 %
P2.2.4.6
AI3 signal inver-
sion
0 1 0 151
0 = Not inverted
1 = Inverted
* = Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle)
PUMP AND FAN CONTROL APPLICATION VACON · 211