1087 SCALING OF GENERATING TORQUE LIMIT 6 (2.2.6.6)
Table 198: Selections for parameter ID1087
Selection
number
Selection name Description
0 Parameter
1 AI1
2 AI2
3 AI3
4 AI4
5 FB limit scaling
This signal will adjust the maximum motor generating torque between 0 and max. limit set
with parameter ID1288. Analogue input level zero means zero generator torque limit. This
parameter is available for NXP drives only.
1088 SCALING OF GENERATING POWER LIMIT 6 (2.2.6.8)
Table 199: Selections for parameter ID1088
Selection
number
Selection name Description
0 Parameter
1 AI1
2 AI2
3 AI3
4 AI4
5 FB limit scaling
This signal will adjust the maximum motor generating power between 0 and max. limit set
with parameter ID1290 This parameter is available for Closed Loop control mode only.
Analogue input level zero means zero generator power limit.
1089 FOLLOWER STOP FUNCTION 6 (2.11.2)
Defines how the follower drive stops (when selected follower reference is not Master's ramp,
parameter ID1081, selection 18).