Table 26: Input signals, G2.2
Index Parameter Min Max Unit Default Cust ID Description
P2.2.2 DIN3 function 0 13 1 301
0 = Not used
1 = Ext. fault, closing
cont.
2 = Ext. fault, open-
ing cont.
3 = Run enable
4 = Acc./Dec. time
select.
5 = Force cp. to IO
6 = Force cp. to key-
pad
7 = Force cp. to
fieldbus
8 = Rvs (if P2.2.1 ≠
2,3 or 6)
9 = Jogging speed
10 = Fault reset
11 = Acc./Dec. oper-
ation prohibit
12 = DC Braking
command
13 = Preset speed
P2.2.3
****
AI1 signal selec-
tion
0.1 E.10 A1 377
TTF programming
method used. See
Chapter 8.9 "Termi-
nal to function" (TTF)
programming princi-
ple
P2.2.4 AI1 signal range 0 2 0 320
0 = 0-10V (0-20
mA**)
1 = 2-10V (4-20
mA**)
2 = Custom setting
range**
P2.2.5
AI1 custom set-
ting minimum
-160.00 160.00 % 0.00 321
Analogue input 1
scale minimum.
P2.2.6
AI1 custom set-
ting maximum
-160.00 160.00 % 100.00 322
Analogue input 1
scale maximum.
P2.2.7
AI1 signal inver-
sion
0 1 0 323
Analogue input 1 ref-
erence inversion
yes/no.
P2.2.8
AI1 signal filter
time
0.00 10.00 s 0.10 324
Analogue input 1 ref-
erence filter time,
constant.
VACON · 78 MULTI-STEP SPEED CONTROL APPLICATION