EasyManuals Logo

Vacon NX series Applications Manual

Vacon NX series
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #79 background imageLoading...
Page #79 background image
Table 26: Input signals, G2.2
Index Parameter Min Max Unit Default Cust ID Description
P2.2.9
****
AI2 signal selec-
tion
0.1 E.10 A.2 388
TTF programming
method used. See
Chapter 8.9 "Termi-
nal to function" (TTF)
programming princi-
ple.
P2.2.10 AI2 signal range 0 2 1 325
0 = 0-10V (0-20
mA**)
1 = 2-10V (4-20
mA**)
2 = Custom setting
range**
P2.2.11
AI2 custom set-
ting minimum
-160.00 160.00 % 0.00 326
Analogue input 2
scale minimum.
P2.2.12
AI2 custom set-
ting maximum
-160.00 160.00 % 100.00 327
Analogue input 2
scale maximum.
P2.2.13
AI2 signal inver-
sion
0 1 0 328
Analogue input 2 ref-
erence inversion
yes/no.
P2.2.14
AI2 signal filter
time
0.00 10.00 s 0.10 329
Analogue input 2 ref-
erence filter time,
constant.
P2.2.15
Reference scaling
minimum value
0.00 320.00 Hz 0.00 303
Selects the fre-
quency that corre-
sponds to the min.
reference signal.
P2.2.16
Reference scaling
maximum value
0.00 320.00 Hz 0.00 304
Selects the fre-
quency that corre-
sponds to the max.
reference signal.
0.00 = No scaling
>0 = scaled max.
value
P2.2.17
Free analogue
input, signal
selection
0 2 0 361
0 = Not used
1 = AI1
2 = AI2
MULTI-STEP SPEED CONTROL APPLICATION VACON · 79
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
4

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled