TITANUS
PRO·SENS
®
Installation
06/13
107
Settings
Detector module
Figure 61: Standard settings on the detector module of TITANUS PRO·SENS
®
Setting of the response sensitivity
The sensitivity of the detector module is set via the switch S1 (1, 2) on the
detector module (refer to Detector module) from TITANUS
PRO·SENS
®
.
The following table shows the response sensitivity (alarm) of TITANUS
PRO·SENS
®
Detector
module
DM-TP-50 L
Detector
module
DM-TP-10 L
Detector
module
DM-TP-01 L
Switch S1
contact 1
SwitchS1
contact 2
0.12 %/m 0.12 %/m on on
0.4 %/m
(standard)
0.06 %/m
(standard)
off on
1 %/m 0. 2 %/m 0.03 %/m on off
0.5 %/m
(standard)
0.12 %/m 0.015 %/m off off
Delay period of the alarm activation
The delay period for the alarm thresholds can be set via the switch S1 (3, 4).
As a standard the delay period for the alarm is set to 10 sec. If the smoke
level increases during operation so that the alarm threshold is reached the
delay period starts. After the delay period has been expired the signal is
6.3
6.3.1
6.3.1.1
6.3.1.2