Connection of the air sampling pipe
Figure 69: Connection of the air sampling pipe to the air sampling smoke detection
system TITANUS PRO·SENS
®
1. To connect the air sampling pipe to TITANUS
®
attach the pipe to the cor-
responding connection (see figure "Connection of air sampling pipe").
NOTICE
Under no circumstances use adhesives to connect the pipe to the connec-
tion piece.
Wide temperature variations make it essential that the pipe is fixed firmly in
place just before the entrance to the device. This will prevent the pipe being
pulled from the device due to fluctuations in pipe lengths (see chapter "In-
stallation of the pipe system").