Design
TITANUS
PRO·SENS
®
84
06/13
Number of aper-
tures
3 6 9 12 15 18
∅ of all aspiration
apertures in mm*)
5,0
3,6
3,0
3,0
2,5
2,5
*) Press cut diameter in aspiration-reducing film sheet
Double - U - Pipe system
1 pipe system and 2 pipe systems
Figure 44: Double U-pipe system, e.g. for equipment protection
Min. distance from TITANUS
to last T-piece 2 m
Max. distance from TITANUS
to last T-piece 20 m
Max. branch length 20 m
Max. overall pipe length Ø 25 mm 100 m
Max. number of aspiration apertures (n) per pipe system 20 no.
Minimum distance between aspiration apertures (d) 0.1 m
Maximum gap between aspiration apertures (d) 4 m
Aspiration apertures
5.3.2.4
pipe systems
Limit values