Commissioning
TITANUS
PRO·SENS
®
166
06/13
Operational check of TITANUS
PRO·SENS
®
If it is not possible to adjust TITANUS
®
check the functionality by means of
the test pipe and a digital manometer or the diagnostic software. For this
check TITANUS
®
must have been in operation for at least 30 minutes.
Preparations for operational check
Figure 97: Operational check of TITANUS PRO·SENS
®
1. Remove the pipe system from TITANUS
®
2. Connect the test pipe.
3. Connect the pressure measuring hose to adapter connection B.
4. Connect the 4-pole plug of the adapter to the digital manometer and
switch on.
NOTICE
For an operational check of TITANUS
®
steps 1 – 4 must be carried out for
the sensor modules of both pipe systems.
8.5
8.5.1