TITANUS
PRO·SENS
®
Design
06/13
65
Sensitivity and pipeline project design
Pipeline project planning with pipe accessories
The following project planning tables for pipeline project planning can be
found in the appendix for each previously selected pipe accessory.
▪ Project planning without filter
▪ Project planning with LF-AD air filter
▪ Project planning with LF-AD-1 air filter
▪ Project planning with LF-AD-2 air filter
▪ Project planning with SF-400 / SF-650 air filter
NOTICE
An area can be monitored with more than detection points than required by
the national guideline in order to improve an air sampling smoke detection
system’s detection quality. In such case, the number of normatively re-
quired sampling points is to be used in calculating the required sensitivity of
an air sampling smoke detection system.
5.2.3