TITANUS
PRO·SENS
®
Design
06/13
73
Special project design
Project planning for individual aperture monitoring
The following system parameters apply to the detection of an individual or a
particular number of blocked aspiration apertures, depending on pipe con-
figuration.
The specifications according to Chapter 5.2 apply to project planning. The
following limit values and aperture diameters should also be taken into ac-
count. Additional accessories (air filters, condensation separators, etc.) can
influence the maximum pipe length.
I - Pipe system
1 pipe system and 2 pipe systems
Figure 37: I-shape pipe system for area protection
Min. distance from TITANUS
– 1. aspiration apertures 4 m
Max. distance from TITANUS
– 1. aspiration apertures 20 m
Max. Distance from 1. aspiration apertures – last aspiration aper-
tures
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
40 m
60 m
Max. Overall pipe length per pipe system
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
60 m
80 m
Min. distance between 2 aspiration apertures (d) 4 m
Max. distance between 2 aspiration apertures (d) 12 m
Max. number of aspiration apertures (n) per pipe system 10 pcs.
5.3
5.3.1
5.3.1.1
Pipe system
Limit values