Electrical connection
In order to prepare the electrical connections follow the steps below:
1. Break through the required cable entries e.g. by means of a screw-
driver.
2. Attach the plastic connection pieces M 20 or M 25 to the cable entries.
3. Pass the cables through the corresponding cable entries.
NOTICE
One plastic connection piece M 20 and 2 x M 25 is supplied with the de-
vice.
The electrical connection is effected via the terminal blocks X6 and X7 on
the main board of TITANUS
PRO·SENS
®
. Pay attention to the allowed wire
cross sections of the corresponding screw joint and to the allowed wire cross
sections of the terminals for max. 1.5 mm² - cores.
WARNING
Connection works are only allowed if the device is powered down!
NOTICE
In order to maximise the fault safety, use shielded cables for the external
wiring of the device(s).