EasyManua.ls Logo

WAGNER TITANUS PRO-SENS - 4 Technical Data; 4.1 TITANUS PRO·SENS Specifications

WAGNER TITANUS PRO-SENS
224 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TITANUS
PRO·SENS
®
Technical Data
06/13
47
Technical Data
NOTICE
All listed power values relate to a surround temperature of 20ºC.
TITANUS
PRO·SENS
®
TITANUS
PRO·SENS
®
TITANUS
PRO·SENS
®
2
supply voltage (Ue)
nominal supply voltage
14 - 30 V DC
24 V DC
U
L
= 6,9 V U
L
= 9 V U
L
= 6,9 V U
L
= 9 V
starting current (at 24 V)
(without reset board)
300 mA 320 mA
current consumption quiescent (at 24
V)
(without reset board)
200 mA
1
275 mA 220 mA 295 mA
current consumption alarm (at 24 V)
(without reset board)
max.
210 mA
max.
285 mA
max.
240 mA
max.
315 mA
current consumption reset board max. 20 mA
load on contact of the
alarm and fault relays
switching power
30 V, 1 A
max. 24 W
(1) The current values may vary
according to the pipe system
UL = fan voltage
dimensions (H x B x T mm) 113 x 200 x 292 mm
weight 1,35 kg
Lpa according to EN ISO 3744, 1995
without noise suppressor
at 45 dB(A)
depending on the configuration and fan voltage
Protection class (DIN IEC 34 part 5) IP 20
material plastic (ABS)
colour papyrus white, RAL 9018
TITANUS
®
deep freeze variety
– 20° to +60°C
– 40° to +60°C
not condensed 10 to 95 % rf
type radial
service life of ventilator (12 V) 43.500 h at 24°C
4
4.1
Voltage
Curren
t
Dimensions
Weigh
t
Noise Level
Protection classification
Housing
Temperature range
Humidit
y
Fan

Table of Contents