TITANUS
PRO·SENS
®
Design
06/13
61
NOTICE
The fire sensitivity classes A, B and C can be achieved with each detector
module available, depending on the number of aspiration apertures.
The table shows the selectable sensitivity levels of the TITANUS
PRO·SENS
®:
Activation sensitivity (fire alarm)
TITANUS PRO SENS®
Detector module
Type DM-TP-50-L
Detector module
Type DM-TP-10-L
Detector module
Type DM-TP-01-L
0.8 % light obscuration/m 0.12 % light obscuration/m
0.4 % light obscuration/m
(Standard)
0.06 % light obscuration/m
(Standard)
1 % light obscuration/m 0.2 % light obscuration/m 0.03 % light obscuration/m
0.5 % light obscuration/m
(Standard)
0.1 %light obscuration/m 0.015% light obscuration/m
Project planning for the monitored surface is always carried out according to
national specifications for point-shaped smoke detectors.
Project planning limits
The following limit values must be complied with at all times with the TITA-
NUS
®
per pipe system connected:
▪ Standard project planning
– The minimum pipe length between 2 aspiration apertures is 4 m.
– The maximum pipe length between 2 aspiration apertures is 12 m.
– The maximum overall pipe length is 200 m
(2 x 200 m with 2 pipe systems connected).
– A maximum of 24 aspiration apertures are possible per detector
module.
▪ Simplified pipe project planning
– The minimum pipe length between 2 aspiration apertures is 0.1 m.
– The maximum pipe length between 2 aspiration apertures is 4 m.
– The maximum overall pipe length is 100 m
(2 x 100 m with 2 pipe systems connected).
– A maximum of 20 aspiration apertures are possible per detector
module.
▪ Project planning with acceleration apertures
5.1.5