Design
TITANUS
PRO·SENS
®
62
06/13
The minimum pipe length between 2 aspiration apertures is 4 m.
The maximum pipe length between 2 aspiration apertures is 12 m.
The maximum overall pipe length is 300 m
(2 x 280 m with 2 pipe systems connected).
A maximum of 100 aspiration apertures are possible per detector
module.
The maximum monitoring area per sampling aperture corresponds to the
monitoring area of point-shaped detectors in accordance with the applicable
project planning guideline.
The maximum overall monitoring area, the maximum overall pipe length and
the maximum number of aspiration apertures are independent of the project
planning selected, as are the restrictions from national regulations.