TITANUS
PRO·SENS
®
Installation pipe system
06/13
131
Installation pipe system
Installation general
The pipes, hoses and fittings used for the pipe system must always meet re-
quirements for Class 1131 in accordance with EN 61386-1, 2004.
Class 1131 puts the following requirements on the pipe system used:
Characteristics Severity code
Compression resistance 125 N
Impingement resistance 0.5 kg, drop height at 100 mm
Temperature range -15 °C to +60 °C
In principle, the following pipes as well as the related fittings are to be used
in configuring the pipe system:
External diameter Internal diameter
ABS
Internal diameter
PVC
Air sampling pipe 25 mm 21.4 mm 21.2 mm
Air sampling hose
(SCH-P-25)
25 mm - 18.5 mm
Air sampling hose
(SCH-PG16)
21.1 mm 16.4 mm -
The following pipes and related fittings are to be used for pipe systems with
long pipe intake line (see also Chapter Design “Project planning with long
pipe intake line”):
External diameter Internal diameter
ABS
Internal diameter
PVC
Air sampling piper 32 mm 28 mm 28,4 mm
Air sampling pipe 40 mm 35 mm 36,2 mm
7