4. The pipes must be installed in such a way that they do not sag or move.
They are fixed with pipe clips without rubber core. The space between
the pipes clips should be no more than 80 cm. Reduce the space be-
tween clips to no more than 30 cm if there are high temperature varia-
tions.
NOTICE
Do not use pipe clips with rubber cores as these do not expand lengthwise
and the pipes would sag or crack.
5. Close open pipe ends with end caps.
NOTICE
After pipe installation is complete, check for the following:
- air tightness (e.g. due to damage)
- any faulty connections
- correct projection of the aspiration aperture
Installation air sampling hose
The air sampling hose should be used in compliance with the design guide-
lines (see chapter "Design").
1. Cut the air sampling hose with a pipe cutter or a metal saw. Chips must
be removed and rough edges trimmed.
2. Before gluing, remove any dirt and grease from the joints with the rec-
ommended cleaning agent. Glue the hose ends to the corresponding fit-
tings so that they are airtight.
air sampling
hose halogen
free
Air sampling
hose (PVC)
Cleaning agent Adhesive Pipe cutter
SCH-PG16 SCH-P-25 Tangit cleaner Tangit adhesive Pipe cutter
or
38 mm
saw