Maintenance
Visual check
Check that
the pipe system is easily accessible, undamaged and firmly installed.
the air sampling points on the pipe system are not blocked.
air sampling pipe and connection cable are tight.
the device support (if installed)
is fastened properly.
the air sampling smoke detection system is not damaged.
(see flash code table)
Flash Code Table
The detector modules are equipped with an LED which indicates different
faults and device conditions in a flash code:
Flash Codes
Number Meaning
Permanently lit Hardware defect in the detector module
2 x Flashing Air flow too small (blockage)
3 x Flashing Air flow too large (fracture)
4 x Flashing Stabilizing phase after turning on, or fan is turned off
Figure 98: Position flash code LED on the detector module