Installation pipe system
TITANUS
PRO·SENS
®
148
06/13
Noise suppressor
Figure 88: Mounting of noise suppressor
1. Remove the pre-punched pipe lead-through in the protection grid of the
air outlet (e.g. with a small side cutter).
2. Pass the pipe (Ø 25 mm) through the opened feed-through in the protec-
tion grid and fixes it with the existing pipe collar in the air outlet of TITA-
NUS
®
. As the air return pipe fits exactly into the exit air opening, a tight
fit is ensured.
3. In order to connect the aspiration pipe with the noise suppressor please
insert the aspiration pipe into the designated pipe connectors of the
noise suppressor.
4. When installing the absorbing duct, ensure that the direction of air flow is
shown at the side of the housing’s bottom part.
5. Screw the bottom part of the housing directly to the wall.
NOTICE
Never use glue to connect the air sampling pipe and pipe connectors.
If severe variations in temperature are expected, then it is required to fix
the pipe right before the air filter in order to avoid elongation ( See chapter
installation of the pipe system “Linear expansion of the pipe system”) of the
pipe and therefore possible loss of pipe connectivity (pipe contraction).
7.8

Table of Contents