Mounting location
Fixing of the TITANUS
PRO·SENS
®
When choosing the mounting location, make sure that the displays are
clearly visible. Screw the air sampling smoke detection system either directly
to the wall with its bottom casing or mount it with a special support (see
chapter Technical Description "Device Support").
NOTICE
Ensure that the mounting location is not within the opening range of any
doors.
Figure 66: Installation of TITANUS PRO·SENS
®
Make sure the air outlet of the system is not blocked. The distance between
the air outlet of TITANUS
®
and adjacent objects (e.g. wall) must be at least
10 cm.
The air sampling smoke detection system TITANUS
®
can be mounted with
the air sampling pipe connectors pointing upwards or downwards. If neces-
sary, turn the lid by 180°.
If TITANUS
®
is mounted with the air sampling pipe connectors pointing
downwards, ensure that no impurities or dripping water enter the upward-
pointing air outlet. For this purpose use a short downward curving pipe.
6.5
6.5.1
A
spiration downward