Technical Manual
Air sampling smoke detection system
®
TITANUS MICRO·SENS

Table of Contents

Question and Answer IconNeed help?

Do you have a question about the WAGNER TITANUS and is the answer not in the manual?

WAGNER TITANUS Specifications

General IconGeneral
Power Supply24 V DC
Operating Temperature-20°C to +60°C
Alarm OutputRelay contacts
CertificationVdS, EN 54
Humidity Range10% to 95% (non-condensing)

Summary

General Information

Introduction to TITANUS MICRO·SENS

Overview of the aspirating smoke detection system and its intended use for installers.

Safety Information and Symbols

Details on symbols used in the manual to highlight important safety and operational information.

Guarantee and Liability Conditions

Information regarding warranty terms, exclusions, and liability for damages.

Copyright and Usage Restrictions

Defines the copyright ownership and rules for reproduction or distribution of the manual.

Packaging and Disposal Guidelines

Instructions on handling packaging materials and proper disposal of the product components.

Product Description and Application

TITANUS MICRO·SENS Characteristics

Details on system features like fire location, sensitivity, signal processing, and airflow monitoring.

Areas of Application for Smoke Detection

Outlines suitable environments and conditions for using the aspirating smoke detection system.

Technical Description of the System

System Overview and Components

Describes the main components of the system, including detection unit, device base, and pipe system.

System Functionality and Operation

Explains the operational phases and principles, including ROOM·IDENT technology.

TITANUS MICRO·SENS Accessories

Details various optional accessories and their overview, such as relay boards and detector boxes.

Detector Box Functionality

Explains the use of external detector boxes for system configuration and sensitivity enhancement.

Diagnostics Tool Usage

Information on using the diagnostic tool for configuration, maintenance, and fault analysis.

Parallel Displays and Indicators

Describes the function and connection of parallel displays and reaction indicators.

Pipe System Overview and Components

Details the pipe system components and their general arrangement for smoke detection.

Aspiration Apertures and Reduction Films

Explains the design and installation of aspiration apertures, including reduction films and clips.

Air Filters for Dusty Environments

Describes the types of air filters used to protect the system in dusty conditions.

Noise Suppressor Installation

Details the mounting and purpose of the noise suppressor for low-noise applications.

Steam Trap for Humid Areas

Explains the function and installation of a steam trap to manage condensation in humid environments.

Technical Data and Specifications

TITANUS MICRO·SENS Technical Specifications

Provides detailed technical data including voltage, current, dimensions, weight, and protection class.

TITANUS MICRO·SENS Detection Box Data

Specific technical data for the detection box, including power, dimensions, and temperature range.

Accessory Technical Data

Technical specifications for various accessories like parallel displays and relay boards.

Pipe System Specifications

Details on pipe length, aperture count, temperature range, and monitoring surface area.

Design and Project Planning

General Design Principles

Introduction to project planning for air sampling smoke detection systems according to EN 54-20.

Regulations for Fire Detection Systems

Lists applicable national and international regulations for planning and installation.

Pipe System Design Considerations

Guidelines for symmetrical and asymmetrical pipe system layouts and aperture planning.

Air Flow Monitoring Procedures

Details on air flow monitoring requirements and adjustments according to EN 54-20.

Sensitivity Settings and Classes

Defines fire sensitivity classes and adjustable sensitivities for detection units.

Design Limits and Parameters

Specifies minimum and maximum limit values for pipe length, apertures, and monitoring areas.

Project Planning Guidelines

General guidelines and factors to consider for project planning, including accessory selection.

Pipeline Project Planning with Accessories

Methodology for planning pipe systems incorporating various pipe accessories like air filters.

Aperture Diameter Specifications

Provides tables for determining aspiration aperture diameters based on pipe configuration.

Special Project Planning for Individual Apertures

Parameters and limit values for planning individual aperture monitoring scenarios.

Simplified Pipe Design Methods

Details on simplified pipe designs for equipment protection in small areas.

Design for Forced Air Flow

Guidelines for designing systems in air conditioning ducts with forced air flow.

Power Supply Sizing and Calculation

Formulas and considerations for calculating power supply requirements for the detection system.

Installation Procedures

General Installation Guidelines

General rules and considerations before starting the installation process.

Selecting the Installation Site

Criteria for choosing an appropriate installation location for the smoke detector.

Connecting the Air Sampling Pipe

Step-by-step instructions for connecting the air sampling pipe to the detection unit.

Connecting Additional Modules Electrically

Guide for making electrical connections for additional modules and components.

Connecting to CFDU with Reset Button

Wiring diagram and instructions for connecting to a CFDU and using a reset button.

Incorporating the Reset Board

Procedure for installing and connecting the reset board for line monitoring.

Incorporating Reset and Isolating Button Board

Instructions for fitting the reset and isolating button board into an additional housing.

Relay Board RU-1/RU-2 Installation

Steps for fitting the relay boards RU-1 and RU-2 into an additional housing.

Using TITANUS MICRO·SENS with AlgoRex Systems

Options for connecting the system to the AlgoRex fire alarm system.

Installing AlgoRex Line Components

Procedure for installing AlgoRex line components into the additional housing.

TITANUS MICRO·SENS and AnalogPLUS Technology

Describes the connection and use of AnalogPLUS technology with the system.

TITANUS MICRO·SENS and Interactive Technology

Details the integration and use of interactive technology with the system.

Connecting TITANUS MICRO·SENS in a Network

Explains how to connect multiple units into a network for monitoring.

Connecting Parallel Displays

Instructions for connecting parallel displays to the detection unit.

Electrical Connection of Parallel Displays

Details the electrical connections for parallel displays via terminal blocks and indicator bus.

Reaction Indicator Addressing

Guide on addressing reaction indicators using switch settings.

Inserting the Detection Unit

Procedure for correctly inserting the detection unit into the device base unit.

System Settings Configuration

Overview of system settings adjustable via the diagnostic tool.

Setting Detection Unit Parameters

Details on configuring sensitivity, alarm delays, air flow thresholds, and fault display.

Configuring Dynamic Air Flow and LOGIC·SENS

Instructions for activating/deactivating dynamic air flow, ROOM·IDENT, and LOGIC·SENS features.

Setting Ventilator Voltage and Air Pressure

Guide on setting ventilator voltage, air pressure, and height for optimal performance.

Data Logging Procedures

Instructions for performing device checks and logging data using the diagnostic tool.

Pipe System Installation

Pipe System Requirements and Components

Details on pipe requirements, external/internal diameters, and installation instructions.

Linear Expansion of Pipe System

Explains how temperature variations affect pipe length and how to calculate expansion.

Patented Air Sampling Points Installation

Instructions for designing and positioning air sampling points with aspiration-reducing films.

Ceiling Lead Through Installation

Procedure for installing ceiling feed-throughs for concealed pipe system mounting.

Monitoring in Forced Air Flow Systems

Guidelines for system design in air conditioning ducts with ventilation or climatic applications.

Air Filter Installation for Dusty Areas

Instructions for installing LF-AD-x and SF-400/650 filters to protect the system.

Air Return for Pressure Differences

Explains the air return system for managing pressure differences and air pollution.

Noise Suppressor Mounting

Details on how to mount the noise suppressor to reduce noise emissions.

3-Way Ball Valve Installation

Instructions for installing and connecting a 3-way ball valve for blow-through processes.

Steam Trap Installation for Humid Areas

Guide for installing a steam trap to eliminate water vapor from the pipe system.

Test Adapter Installation

Instructions for installing and using the test adapter for maintenance and service.

Commissioning Procedures

Commissioning the Detection Unit

Steps for preparing and commissioning the detection unit, including pipe system checks.

Plug and Play Commissioning

Describes the automatic commissioning process using the Plug and Play function.

Commissioning with Diagnostics Tool

Procedure for commissioning using the diagnostic tool, allowing settings adjustments.

Installing Diagnostics Software

Instructions for installing the diagnostic software on a PC or laptop.

Air Flow Sensor Adjustment Process

Details on adjusting the air flow sensor for optimal performance and stability.

Air Pressure-Independent Adjustment

Describes the automatic adjustment of the air flow sensor independent of ambient air pressure.

Air Pressure-Dependent Adjustment

Instructions for adjusting the air flow sensor based on ambient air pressure using a barometer.

Testing Detection Unit and Alarm Forwarding

Procedures for testing the detection unit's functionality and alarm signal transmission.

Testing Air Flow Monitoring Functionality

Steps to test the air flow monitoring for pipe breaks and blockages.

Testing Fault Forwarding

Procedure to verify that fault signals are correctly forwarded to the FAS.

Testing Air Flow Sensory Analysis

Detailed steps for testing the air flow sensory analysis function using test equipment.

Commissioning Fire Seat Location

Procedure for commissioning the fire seat location feature using the ROOM·IDENT screen.

Commissioning Reaction Indicators

Steps for commissioning and testing reaction indicators for fire location indication.

Maintenance and Servicing

Visual Inspection Checklist

Guidance for performing visual checks on the system components for proper mounting and condition.

Testing Detector and Alarm Forwarding

Procedure for testing the detector and alarm forwarding functionality.

Testing the Pipe System for Blockages

Instructions for testing and clearing pipe system blockages using compressed air.

Exchanging the Detection Unit

Step-by-step guide for replacing the detection unit.

Changing Air Filters

Instructions for changing air filters (LF-AD-x and SF-400/650) for system maintenance.

Pipe System Blow Through Process

Procedure for manually blowing through the pipe system to clear debris.

Checking Air Flow Sensor Adjustment

Procedure for checking and verifying the air flow sensor adjustment using diagnosis software.

Testing Fire Seat Location and Reaction Indicators

Steps for testing the fire seat location and reaction indicators functionality.

Testing Air Flow Monitoring

Procedure for testing the air flow monitoring function for breaks or blockages.

Testing Fault Forwarding

Procedure for testing the forwarding of fault signals.

Maintenance Intervals Schedule

Overview of recommended maintenance intervals for inspections and servicing.