TITANUS MICRO·SENS
®
Technical Description
MS_A_02-a-en-e Data: 01/09 2 – 1
2 Technical Description
2.1 System Description
The TITANUS MICRO·SENS
®
aspirating smoke detection system
comprises a detection unit, device base and pipe system.
The most important components of the TITANUS MICRO·SENS
®
are the
sensitive detection unit for picking up smoke aerosols and the aspiration
unit with integrated air flow sensor for transporting air samples and for
monitoring the pipe system for breaks and blockages .
The pipe system consists essentially of pipe and fittings, in either PVC or
ABS plastics.
ir aspiration
Air outlet
Aspiration unit
Detection unit
spiration apertures
Aspiration pipe
Pipe system
Accessories
Detection unit
and
Device base
Detection
incl. air flow sensor
Reaction
indicator
Device base
TITANUS MICRO·SENS
®
E
D
C
B
A
10
9
8
7
6
5
4
3
2
1
Parallel display
Fig. 2.1: Overview of the TITANUS MICRO·SENS
®
smoke detection system
To guarantee safe operation even under the most difficult conditions (e.g.
recycling area), there are extensive accessories available such as, e.g.,
an integrated air filter, various external air filters or the blow through
device. In very cold areas, a deep freeze version of the TITANUS
MICRO·SENS
®
can be used. A redundancy ventilator can be used for
applications where there are particular safety requirements.
When fitted to monitor several monitoring areas and blind spots, there
are reaction indicators for rapid identification of the seat of the fire and an
offset parallel display as a status indicator for the detection unit.