Technical Description TITANUS MICRO·SENS
®
2 – 18 Data: 01/09 MS_A_02-b-en-e
2.3.2.2 Aspiration reduction clips
air flow reducer for deep freeze storage areas
plastic clip for air flow reducer
Fig. 2.25: Aspiration reduction for dirty areas and deep freeze areas
The aspiration apertures used in areas where there may be blockages
are fitted with a patented type AK-C plastic clip and a patented type AK-x
flexible aspiration reduction (see
0HFig. 2.25). The aspiration reducers are
available in defined, stepped aperture diameters.
With blowing through, the flexible aspiration reducer stretches to the
aspiration apertures. In deep freeze areas this leads to icing breaking off
and in very dusty areas to dirt breaking off. The special plastic clip is for
fixing the aspiration reduction to the pre-defined point.
When designing for areas with environmental influences which make
blowing through necessary (e.g. dust) or very humid areas, the aspira-
tion reducers with a plastic clip are to be preferred over aspiration reduc-
tion films with banderol. The plastic clips have greater resistance when
subject to pressure stress. There is also a greater cleaning effect thanks
to the elastic rubber insert.