EasyManua.ls Logo

WAGNER TITANUS - Monitoring in Forced Air Flow Systems

WAGNER TITANUS
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TITANUS MICRO·SENS
®
Installation Pipe System
MS_A_06-en-e Data: 01/09 6 – 9
6.4 Monitoring in forced air flow systems
(ventilation or climatic applications)
6.4.1 Detection at air inlets/outlets
If aspiration takes place in a forced air flow system (ventilator, climatic
systems), the air sampling points must be positioned in the air flow. Pla-
ce the air sampling points as shown in fig. 6.5.
Fig. 6.5: Positioning of air sampling point, depending on air speed
6.4.2 Detection in bypass systems
For connection of air return refer to chapter 6.6 "Air Return".
Fig. 6.6: Positioning of air return, example of a climatic duct (bypass)
For the pipe design of TITANUS MICRO·SENS
®
in these areas see chap-
ter 4.3.4 “Pipe Design for Forced Air Flow“.
INSTRUCTION

Table of Contents

Related product manuals