Technical Data
MS_A_03-en-e Data: 01/09 3 – 1
3 Technical Data
All power consumption figures relate to an ambient temperature of 20°C.
3.1 TITANUS MICRO·SENS
®
TITANUS MICRO·SENS
®
Voltage
Power supply (Ue)
Nominal power supply
16 to 30 V DC
24 V DC
Current
U
L
0F
1
= 9 V
(at 24 V)
U
L
= 10.5V
(at 24 V)
U
L
= 12 V
(at 24 V)
U
L
= 13.5V
(at 24 V)
Starting current1F
2
150 mA
Power consumption at idle status
2
105 mA 125 mA 145 mA 170 mA
Power consumption at alarm status
2
Device variant with fire alarm
110 mA
130 mA
150 mA
175 mA
Power consumption at alarm status
2
fire alarm, smoke level
140 mA
160 mA
180 mA
205 mA
Outputs
Contact loading capacity of the
alarm and fault relay
1A / 30VDC
Dimension
Dimensions (H x W x D mm) 70 x 140 x 222 mm
Weight
Weight 0.8 kg
Sound intensity level
L
wa
as per EN 27779, 1991 40 dB(A) at 9V
Protection class
Protection class (EN 60 529)
without air return
with pipe piece 100 mm/pipe bend
with air return
IP 20
IP 42
IP 54
1
U
L
= Ventilator voltage
2
without extra module
INSTRUCTION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER TITANUS and is the answer not in the manual?

WAGNER TITANUS Specifications

General IconGeneral
Power Supply24 V DC
Operating Temperature-20°C to +60°C
Alarm OutputRelay contacts
CertificationVdS, EN 54
Humidity Range10% to 95% (non-condensing)