EasyManua.ls Logo

WAGNER TITANUS - Technical Data and Specifications; TITANUS MICRO·SENS Technical Specifications

WAGNER TITANUS
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TITANUS MICRO·SENS
®
Technical Data
MS_A_03-en-e Data: 01/09 3 – 1
3 Technical Data
All power consumption figures relate to an ambient temperature of 20°C.
3.1 TITANUS MICRO·SENS
®
TITANUS MICRO·SENS
®
Voltage
Power supply (Ue)
Nominal power supply
16 to 30 V DC
24 V DC
Current
U
L
0F
1
= 9 V
(at 24 V)
U
L
= 10.5V
(at 24 V)
U
L
= 12 V
(at 24 V)
U
L
= 13.5V
(at 24 V)
Starting current1F
2
150 mA
Power consumption at idle status
2
105 mA 125 mA 145 mA 170 mA
Power consumption at alarm status
2
Device variant with fire alarm
110 mA
130 mA
150 mA
175 mA
Power consumption at alarm status
2
fire alarm, smoke level
140 mA
160 mA
180 mA
205 mA
Outputs
Contact loading capacity of the
alarm and fault relay
1A / 30VDC
Dimension
Dimensions (H x W x D mm) 70 x 140 x 222 mm
Weight
Weight 0.8 kg
Sound intensity level
L
wa
as per EN 27779, 1991 40 dB(A) at 9V
Protection class
Protection class (EN 60 529)
without air return
with pipe piece 100 mm/pipe bend
with air return
IP 20
IP 42
IP 54
1
U
L
= Ventilator voltage
2
without extra module
INSTRUCTION

Table of Contents

Related product manuals