Technical Data TITANUS MICRO·SENS
®
3 – 2 Data: 01/09 MS_A_03-en-e
TITANUS MICRO·SENS
®
Housing
Material Plastic (ABS)
Colour Housing papyrus white, RAL 9018
Temperature range
TITANUS MICRO·SENS
®
Deep freeze version
– 20° to +60° C
– 40° to +60° C
Humidity
not condensed max. 95 % rf (without dew)
Ventilator
Type of construction axial
Lifetime of ventilator (12V) 60.000 h at 24° C
Displays on device
Operation
Fire alarm
Action alarm
Fault
Smoke level display
Alarm location display
green operating display
red alarm display
red alarm display (optional)
yellow collective fault
yellow smoke level display 1 to 10
(10 segments) (optional)
5 red displays
(optional)
Infrared interface
Infrared interface IR
Transmitter/ Receiver
Connections
Device connection Clips for
0.5 – 2.5 mm² wires
Cable pair twisted,
Cable feeds
device base
Device base floor
8 x M 20
2 x M 25
4 x M 25
conical pipe plug-in connections
1 x for aspiration pipe
25 mm and
1x air return
25 mm
Reaction sensitivity
Detection unit
DM-TM-10 0.1 to 2.0 % light obscuration/m
DM-TM-50 0.5 to 2.0 % light obscuration/m