TITANUS MICRO·SENS
®
Product Description
MS_A_01-en-e Data: 01/09 1 – 1
1 Product Description
1.1 Characteristics of the TITANUS
MICRO·SENS
®
aspirating smoke
detection system
TITANUS MICRO·SENS
®
is the latest generation of the renowned
WAGNER smoke detection systems. The TITANUS MICRO·SENS
®
can
be used for room and equipment protection and for monitoring air condi-
tioning cabinets or air conditioning ducts. Through the innovative
ROOM·IDENT process, the system can also locate the site of the fire.
Locating the site
of the fire The unique ROOM·IDENT technology makes it possible to determine the
location of a fire when monitoring up to 5 separate areas. So that the
emergency services can act as quickly as possible, the seat of the fire
can be made known, for example, via reaction indicators which are allo-
cated to the various monitoring areas.
Sensitivity The TITANUS MICRO·SENS
®
reaction threshold can be set at between
0.1 %/m and 2 %/m light obscuration in steps of 0.1%/m. Using a smoke
level indicator, an indicator sensitivity of between 0.05 %/m and 0.2 %/m
light obscuration can be achieved. The HIGH POWER LIGHT SOURCE
light source technology used in TITANUS
®
systems guarantees homoge-
neous reaction behaviour from different types of fire. The device can pro-
vide 2 alarm thresholds (pre alarm and alarm). The pre-alarm threshold is
adjustable from 10 - 80 % of the fire alarm threshold.
Intelligent
signal processing The TITANUS MICRO·SENS
®
has LOGIC·SENS intelligent signal
processing for avoiding false alarms. Perfected algorithms based on
numerous fire trials and decades of experience ensure a high level of
safety in differentiating between a false status and a fire event.
Safe airflow
monitoring PIPE·GUARD, the comprehensive package for airflow monitoring,
recognises safe breakdowns such as pipe breakages or blocked
detection apertures. Using dynamic airflow monitoring, the TITANUS
MICRO·SENS
®
reacts even to small, quick changes in the airflow and
thus makes an important contribution to sabotage safety.
Airflow monitoring is temperature-compensated and can be set to be air
pressure-dependent.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER TITANUS and is the answer not in the manual?

WAGNER TITANUS Specifications

General IconGeneral
Power Supply24 V DC
Operating Temperature-20°C to +60°C
Alarm OutputRelay contacts
CertificationVdS, EN 54
Humidity Range10% to 95% (non-condensing)