Installation TITANUS MICRO·SENS
®
5 – 36 Data: 01/09 MS_A_05-en-e
5.13.1.12 Inputting the current air pressure
The current air pressure for the monitoring area must be input by using
the TITANUS MICRO·SENS
®
diagnostic tool if air pressure-dependent
adjustment is required.
The standard setting is 1013 hPa, corresponding to the average air
pressure at sea level.
5.13.1.13 Inputting height above Normal Sea Level (NN)
The figure for the height above normal sea level is that for the installation
site of the TITANUS MICRO·SENS
®
above sea level. The figure is input
by using the diagnostic tool. The standard setting is 0 m. The figure has
to be changed if the device’s air flow sensory analysis has to be balanced
because of the air pressure (see Chap.7).
If the standard setting for air pressure or the height above sea level is
changed, the TITANUS MICRO·SENS
®
air flow is automatically
re-initialised.
ATTENTION