TITANUS MICRO·SENS
®
Commissioning
MS_A_07-en-e Data: 01/09 7 – 11
7.7 Testing the air flow sensory analysis
function
If the TITANUS MICRO·SENS
®
cannot be adjusted, test how it is
functioning by means of a test pipe, a digital precision manometer, a PC
and the diagnosis tool.
Complete function testing using the digital precision manometer is
described below. Limited function testing can also be carried out without
the digital precision manometer.
7.7.1 Preparations for function testing
1. Release the pipe system from the TITANUS MICRO·SENS
®
.
After the pipe system is released from the TITANUS MICRO·SENS
®
and
the air flow fault delay time has elapsed, it signals a fault. If no air flow
fault is recognised, the device is defective.
B
A
P
a
G
D
H
0
1
A
N
G
R
E
I
S
IN
G
E
R
e
l
e
c
t
r
o
n
i
c
e
G
4
2
3
ø 7.0 mm
ø 4.2 mm
ø 4. 6 mm
Testing pipe for ADx, TITANUS
type PFR
Pressure measuring hose
Adapter
Digital manometer
type GDH 01 AN
Air sampling point
Fig. 7.3: Checking the functioning of the TITANUS MICRO·SENS
®
2. Connect the test pipe.
3. Attach the pressure measuring tube to the adapter connection B. For
limited function testing without the digital precision manometer, the
pressure measuring tube connection on the test pipe is to be closed.
INSTRUCTION