TITANUS MICRO·SENS
®
Pipe Design
MS_A_04-en-e Data: 01/09 4 – 25
4.3.1.4 Double-U-Pipe system
1 Pipe system
TITANUS
MICRO·SENS
P
®
P
B
d
TITANUS
®
Fig. 4.9: Double-U-Pipe system for area protection
Limit values
min. distance TITANUSP
®
P
– T piece 2 m
max. distance TITANUSP
®
P
– T piece 20 m
max. branch length 12,5 m
max. overall pipe length per pipe system
Pipe ∅ 25 mm plus
pipe ∅ 12 mm
50 m
8 x 3 m
max. overall pipe length per pipe system with a ventilator
voltage of <10.5 V
Pipe ∅ 25 mm plus
pipe ∅ 12 mm
40 m
8 x 3m
min. distance between 2 aspiration apertures (d) 4 m
max. distance between 2 aspiration apertures (d) 10 m
max. number aspiration apertures (n) per pipe system 8 no.
Aspiration apertures
Number of apertures
per pipe system
4 8
∅ Aspiration aperture
in mm
TP11F
12
PT)
A
B
4,4
—
3,0
3,2
TP
12
PT Opening diameter of the aspiration reduction film