Pipe Design TITANUS MICRO·SENS
®
4 – 26 Data: 01/09 MS_A_04-en-e
Trigger Thresholds Double U-pipe System
per pipe system
Number apertures 4 8
1 blocked aperture
±15 %
—TP12F
13
PT
2 blocked apertures
±30 % ±15 %
3 blocked apertures {TP13F
14
PT
±25 %
4 blocked apertures
{
±35 %
5 blocked apertures
{ {
6 blocked apertures
{ {
… is/are recognised if main air flow set to x %
Example If the blockage of 3 aspiration apertures out of a total of 8 aspiration
apertures is recognised, then with the aid of the diagnosis tool air flow
monitoring can be set to ±25 %.
For a project planning according to EN 54-20, the air flow monitoring
has to be adjusted to ≤20 % in either case.
TP
13
PT — not possible
TP
14
PT { not sensible