Pipe Design TITANUS MICRO·SENS
®
4 – 24 Data: 01/09 MS_A_04-en-e
Trigger Thresholds M-pipe System
per pipe system
Number apertures 3 6
1 blocked aperture
±30 % ±15 %
2 blocked apertures { TP10F
11
PT
±30 %
3 blocked apertures
{ {
4 blocked apertures
{ {
5 blocked apertures
{ {
6 blocked apertures
{ {
… is/are recognised if main air flow set to x %
Example If the blockage of 1 aspiration apertures out of a total of 6 aspiration
apertures is recognised, then with the aid of the diagnosis tool, air flow
monitoring can be set to ±
15 %.
For a project planning according to EN 54-20, the air flow monitoring
has to be adjusted to ≤20 % in either case.
TP
11
PT { not sensible
INSTRUCTION