EasyManuals Logo

WAGNER TITANUS User Manual

WAGNER TITANUS
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #173 background imageLoading...
Page #173 background image
Projection without filter
Number of points
Type
Sensitivity
(% Lt/m)
1 2 3 4 5 6 7 8
0,1 A A A A A A A A
0,2 A A A A A A B B
0,3 A A A A B B B B
DM-TM-10
0,4
A A A B B B B C
0,5 A A B B B B
C
C
0,6 A A
B
B
B
C C C
0,7 A
B
B B C C C C
0,8 A
B
B C C C C C
0,9 A
B
B C C C C C
1 A
B
B C C C C C
1,1 A
B
C C C C C C
1,2 A
B
C C C C C C
1,3
B
B C C C C C
1,4
B
B C C C C
1,5
B
B C C C C
1,6
B
C C C C C
1,7
B
C C C C
1,8
B
C C C C
1,9
B
C C C C
DM-TM-50
2
B
C C C
without pipe accessories or with detector box or VSK
Pipe shape
U
Fan
[V]
1 2 3 4 5 6 7 8
I
9
40 40 40 40 40
U
9
50 50 50 50 50 50 50 50
M
9
50 50 50 50 50 50 50 50
Double U
9
50 50 50 50 50 50 50 50
permitted total pipe
length [m]
with OXY·SENS and detector box or with steam trap or with VSK and detector box
Pipe shape
U
Fan
[V]
1 2 3 4 5 6 7 8
I
9
40 40 40
U
9
50 50 50 50 50 50
M
9
50 50 50 50 50 50
Double U
9
50 50 50 50 50 50 50 50
permitted total pipe
length [m]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER TITANUS and is the answer not in the manual?

WAGNER TITANUS Specifications

General IconGeneral
Power Supply24 V DC
Operating Temperature-20°C to +60°C
Alarm OutputRelay contacts
CertificationVdS, EN 54
Humidity Range10% to 95% (non-condensing)

Related product manuals