Projection with air filter LF-AD
Number of points
Type
Sensitivity
(% Lt/m)
1 2 3 4 5 6 7 8
0,1 A A A A A A A A
0,2 A A A A A B B B
0,3 A A A B B B B B
DM-TM-10
0,4
A A B B B B C C
0,5 A A B B B C
C
C
0,6 A B
B
B
C
C C C
0,7 A
B
B C C C C C
0,8 A
B
B C C C C C
0,9 A
B
C C C C C C
1 A
B
C C C C C C
1,1 B
B
C C C C C
1,2 B
B
C C C C
1,3
B
C C C C C
1,4
B
C C C C
1,5
B
C C C C
1,6
B
C C C C
1,7
B
C C C
1,8
B
C C C
1,9
B
C C C
DM-TM-50
2
B
C C C
without additional pipe accessories or with detector box or VSK
Pipe shape
U
Fan
[V]
1 2 3 4 5 6 7 8
I
9
40 40 40 40 40
U
9
50 50 50 50 50 50 50 50
M
9
50 50 50 50 50 50 50 50
Double U
9
50 50 50 50 50 50 50 50
permitted total pipe
length [m]
with OXY·SENS and detector box or with steam trap or with VSK and detector box
Pipe shape
U
Fan
[V]
1 2 3 4 5 6 7 8
I
9
40 40 40
U
9
50 50 50 50 50 50
M
9
50 50 50 50 50 50
Double U
9
50 50 50 50 50 50 50 50
permitted total pipe
length [m]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WAGNER TITANUS and is the answer not in the manual?

WAGNER TITANUS Specifications

General IconGeneral
Power Supply24 V DC
Operating Temperature-20°C to +60°C
Alarm OutputRelay contacts
CertificationVdS, EN 54
Humidity Range10% to 95% (non-condensing)