TITANUS MICRO·SENS
®
Maintenance
MS_A_08-en-e Data: 01/08 8 – 5
8.7 Changing the filter on the SF-400/650
special filter
Aspiration pipe
Special filter for
ADx und TITANUS
type SF-400
type SF-650
®
1a
2
Fig. 8.6: Changing the filter element
To change the filter element, proceed as follows:
1
Loosen the two PVC transition threaded joints on the special filter
and remove it .
2
Loosen both screwed plugs on the filter housing.
3
Remove the old filter element. Put the new filter element into the
filter housing.
4
Screw both screwed plugs to the filter housing.
5
Replace the special filter in the pipe system and fix it with the PVC
transition threaded joints.
When the special filter is being installed, pay attention to the throughflow
direction!
Opening the special filter will produce an air flow fault on the TITANUS
MICRO·SENS
®
.