Installation
TITANUS
PRO·SENS
®
122
06/13
Connection to FAS, with reset button
The relay contacts on the base board can be used to e.g. connect TITA-
NUS
®
to a central fire panel, to trigger signalling devices, security manage-
ment systems etc. It is also possible to connect a response indicator.
NOTICE
The reset input must not be permanently connected to +24 V. Otherwise all
signals – even an alarm – are automatically reset after the cause of the
signal has been eliminated. In this case the alarm is non-latched.
6.6.1