TITANUS
PRO·SENS
®
Maintenance
06/13
173
Exchange of detector module
Figure 99: Exchange of detector module
1. Carry out the following steps only if the device is powered down.
Carefully unlock the snap-in closures of the housing using a screwdriver
by simultaneously pressing in both clips located at one side of the hous-
ing lid. Then, lift the lid carefully.
2. Pull the display board cable off and remove the lid.
3. Pull the connection cable of the detector module off the main board.
4. Carefully spread a bit both support clamps of the detector module and
remove the detector module.
5. Spread both support clamps again, and place the new detector module
in between them so that it audibly snaps in. Afterwards press both sup-
port clamps together.
6. Reconnect the detector module via the ribbon cable to the main board.
Connection: X1 (HEAD 1)
7. Connect the display board to the main board X4 (DISPLAY).
8. Before initialisation, operating power must be re-established. Press the
Flow-Init button S2 at the detector module in order to initialize the pipe
system.
9. Close the housing lid.
9.5