TITANUS
PRO·SENS
®
Design
06/13
83
Number of aper-
tures
2 4 6 8 10 12 14 16 18
∅ of all aspiration
apertures in mm*)
6,0
4,4
3,6
3,2
3,0
3,0
2,5
2,5
2,5
*) Press cut diameter in aspiration-reducing film sheet
M - Pipe system
1 pipe system and 2 pipe systems
Figure 43: M-pipe system, such as for equipment protection
Min. distance from TITANUS
to last T-piece 2 m
Max. distance from TITANUS
to last T-piece 20 m
Max. branch length 20 m
Max. overall pipe length Ø 25 mm 80 m
Max. number of aspiration apertures (n) per pipe system 18 no.
Min. distance between 2 aspiration apertures (d) 0.1 m
Max. distance between 2 aspiration apertures (d) 4 m
spiration apertures
5.3.2.3
pipe systems
Limit values