Commissioning
TITANUS
PRO·SENS
®
162
06/13
Detector module and alarm transmission
Activate the detector module and check the transmission value to the CFDU
as follows:
1. Spray test aerosol either into the first air sampling point or the test
adapter of the TITANUS
®
pipe system.
2. Proceed as follows:
Check that ... If this is not the case ...
the alarm indicator on the detection
system is functional.
1. check that the circuit board is
connected.
2. check if there is a defect in the
detection system.
3. exchange the detector module.
the alarm is transmitted to the CFDU
on the relevant line.
check the transmission lines.
NOTICE
I If the LOGIC·
SENS
SENS switch S1-10 am set to “ON” (see chapter In-
stallation "Settings"), it has to be set to “OFF” when testing with test aero-
sol, so that alarm evaluation can be speeded up.
NOTICE
Record all tested data in the inspection protocol.