TITANUS
PRO·SENS
®
Maintenance
06/13
175
Changing the air filter LF-AD-x
Figure 100: Change the filter inserts
To clean or change the filter inserts, carry out the following steps:
1. Loosen the four screws and remove the housing lid.
2. Remove the filter inserts and checks how soiled they are. The inserts
can be cleaned if there is a small amount of soiling and must be replaced
if soiling is heavy.
3. Carefully clean the inside of the housing from any dust. Replace the
cleaned or replaced filter inserts in the correct sequence, which is shown
on the instruction label of the housing floor.
4. Replace and screw down the housing lid.
TIP
In environments with a high level of fine-grade dust, three optional fine dust
filters can be used in addition.
9.6