TITANUS
PRO·SENS
®
Commissioning
06/13
163
Check air flow monitoring
Verify the detection of a pipe fracture:
1. Loosen the connection between pipe and TITANUS
®
or open the test
adapter.
2. Check that the fault display of the air sampling smoke detection system
is lit.
3. Optionally, check the data of the air flow sensors with the diagnostic
software DIAG 3 and a PC or laptop.
4. Enter the result in the inspection protocol.
Verify the detection of a blockage:
1. Close the required number of air sampling points (depending on the de-
sign for air flow monitoring) with adhesive tape.
2. Check that the fault LED on the smoke detection system lights up.
3. Optionally, check the data of the air flow sensors with the diagnostic
software DIAG 3 and a PC or laptop.
4. Enter the result in the inspection protocol.
NOTICE
A pipe fracture or blockage is indicated by a flashing LED on each detector
module.
- fracture: 3 x flashing
- blockage: 2 x flashing
The relevant flash code is repeated every two seconds.
If faults in the air flow are not correctly detected by the device.
Check that ...
1. all air sampling points are free.
2. the pipe system has no fractures or cracks.
3. all pipe connections are air tight.
4. the ventilator is not blocked.
5. the correct aspiration-reducing film sheets have been used.
8.3
Pipe Fracture
Blockage
Trouble shooting