Installation
TITANUS
PRO·SENS
®
112
06/13
Setting of fan voltage at TITANUS
PRO·SENS
®
-SL
Figure 64: Switching the fan voltage and fan connection terminal board on the FC-2
or FC-3 fan control circuit board
The default setting for the fan voltage is 6.9 V. The fan voltage can be ad-
justed according to project planning by plugging or removing the BR 1 and/or
BR 2 bridges. The symbols used mean:
X = pin pair bridge O = pin pair open
The default setting is indicated by bold type.
Setting of fan voltage
FC-2
Bridge Pin-No.
BR1, 1+2
Bridge Pin-No.
BR2, 1+2
6.5 V O X
6.9 V
(standard)
X O
9 V O O
Setting of fan voltage
FC-3
Bridge Pin-No.
BR1, 1+2
Bridge Pin-No.
BR2, 1+2
10 V O X
11 V (standard) X O
12 V O O
6.3.1.10