TITANUS
PRO·SENS
®
Design
06/13
79
Double U - Pipe system
1 pipe system and 2 pipe systems
Figure 40: Double U pipe system for area protection
Min. distance from TITANUS
– to last T-piece 4 m
Max. distance from TITANUS
– to last T-piece 20 m
Max. branch length
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
20 m
30 m
Max. Overall pipe length per pipe system
with low fan voltage 6,5 V – 6,9 V
with high fan voltage 9 V – 12V
100 m
140 m
Min. distance between 2 aspiration apertures (d) 4 m
Max. distance between 2 aspiration apertures (d) 12 m
Max. number of aspiration apertures (n) per pipe system 12 pcs.
5.3.1.4
Rohrsysteme
Limit values